| C900 SPECIFICATIONS | |||||||
| Schedule or S.D.R. |
Normal Pipe Size Inches |
Outside Diameter Inches |
Bell Length Inches |
Bell Diameter Inches |
Reference Mark Inches |
Min. Walls |
Estimated Weight of Pipe Per Foot (lbs) |
| DR 25 (PC 165) | 4 | 4.800 | 5 | 6.5 | 4.25 | 0.192 | 1.9 |
| DR 18 (PC 235)* | 0.267 | 2.6 | |||||
| DR 14 (PC 305)** | 0.343 | 3.25 | |||||
| DR 25 (PC 165) | 6 | 6.900 | 6.5 | 9.25 | 5.5 | 0.276 | 3.85 |
| DR 18 (PC 235)* | 0.383 | 5.3 | |||||
| DR 14 (PC 305)** | 0.493 | 6.6 | |||||
| DR 25 (PC 165) | 8 | 9.050 | 7.5 | 11.75 | 6.5 | 0.362 | 6.7 |
| DR 18 (PC 235)* | 0.503 | 9.15 | |||||
| DR 14 (PC 305)** | 0.646 | 11.4 | |||||
| DR 25 (PC 165) | 10 | 11.100 | 9 | 14.25 | 8 | 0.444 | 10.15 |
| DR 18 (PC 235)* | 0.617 | 13.8 | |||||
| DR 14 (PC 305)** | 0.793 | 17 | |||||
| DR 25 (PC 165) | 12 | 13.200 | 9.5 | 16.75 | 8.75 | 0.528 | 14.3 |
| DR 18 (PC 235)* | 0.733 | 19.45 | |||||
| DR 14 (PC 305)** | 0.943 | 24.45 | |||||
| Bell lengths and reference marks may vary up to +/- 1/2 inch. | |||||||
| * The DR 18 line of pipe is Pressure Class 150 per Factory Mutual (FM) Standards | |||||||